Published: 18.07.2019
18 (63)
IN1
G0
Input 1 (0...10 V or NTC 10 or digital).
IN2
G0
Input 2 (0...10 V or NTC 10 or digital).
IN3
G0
Input 3 (0...10 V or NTC 10 or digital). The input supports energy harvesting from 0...10 V signal when
the device is battery powered. The harvesting is active if the signal is over 4 V.
Note:
When using 0...10 V inputs, the input potential must be the same that is used in the
connected 0...10 V device. Use common G0 with the connected device's power supply, for
example.
Note:
Use NO type contact for digital input, if the device is only battery powered. NC
requires power and that significantly shortens the battery life.
VCC
3...5 Vdc
SCL
Serial clock line.
SDA
Serial data line.
GND
I2C
models
0 V
G0
0 V
G
10...30 Vdc / 12...28 Vac
3.5 Network configuring and commissioning procedure
It's recommended to follow the following procedure to be able to configure and commission the
wireless network successfully.
1.
Design the network and place the devices.
See the section
on page 12.
2.
Configure the base unit settings.
See the section
Configuring the base unit settings
on page 20.
3.
Set up the network.
See the section
Setting up a new wireless network
on page 46.
4.
Configure transmitter settings.
See the section
Configuring the wireless transmitters
on page 53.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.
EN - 5401comm