Published: 18.07.2019
38 (63)
Regis-
ter
Parameter description
Data type Values
Range
Default
11499
Transmitter value type, ID 100.
Unsigned 16 0 - 1 - 2 - ... -
12
See the list of
available values from
the chapter
38.
0
Holding registers for transmitter specific value over bus 1
The available values depend on the settings made in the chapter
Holding registers for transmitter
specific value over bus 1 configuration
on page 37.
Regis-
ter
Parameter description
Data type Values
Range
Default
11600
Transmitter value to send over bus
1, ID 1.
Unsigned 16 -
-
0
11601
Transmitter value to send over bus
1, ID 2.
Unsigned 16 -
-
0
...
...
...
...
...
...
11699
Transmitter value to send over bus
1, ID 100.
Unsigned 16 -
-
0
Holding registers for transmitter specific value over bus 2
The available values depend on the settings made in the chapter
Holding registers for transmitter
specific value over bus 2 configuration
on page 37.
Regis-
ter
Parameter description
Data type Values
Range
Default
11700
Transmitter value to send over bus
2, ID 1.
Unsigned 16 -
-
0
11701
Transmitter value to send over bus
2, ID 2.
Unsigned 16 -
-
0
...
...
...
...
...
...
11799
Transmitter value to send over bus
2, ID 100.
Unsigned 16 -
-
0
Available value over bus (VOB) value types
Register
value
Value description
Data type Values
Range
0
VOB is not in use.
-
-
-
1
Temperature
Signed 16
-1000...1000
-100,0...100,0 °C
2
Humidity
Signed 16
0...10000
0...100,00 %rH
3
CO
2
Signed 16
0...10000
0...10000 ppm
4
Voltage
Signed 16
0...1000
0...10,00 V
5
Current
Signed 16
0...2000
0...20,00 mA
6
Resistance, low
Signed 16
0...20000
0...2000,0 Ω
7
Resistance, high
Signed 16
0...30000
0...300000 Ω
8
Hot water consumption (Finnish)
Signed 16
0...30000
0...30000 m
3
LV
9
Cold water consumption (Finnish)
Signed 16
0...30000
0...30000 m
3
KV
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.
EN - 5401comm