Published: 18.07.2019
22 (63)
3.
Select the average group type.
The available types are:
Disabled
Average group disabled.
Temperature
Average group for temperature measurements.
Relative Humidity
Average group for relative humidity measurements.
CO2
Average group for CO
2
measurements.
4.
Press the
Edit parameters
button.
5.
Make the settings.
See the chapter
Available settings for average groups
on page 22 for more details.
6.
Press the
Confirm changes
button to save the changes.
7.
Press the
Confirm changes
button again to save the changes.
8.
Press
Install to device
button to write the changes to the device.
4.1.1 Available settings for average groups
Parameter name Values
Default
Description
Average calculation
source selection
Internal / External
1...4
Internal
Source for the measurement.
Internal
= internal
measurement.
External
= external measurement.
External measurements are available for the
devices that have inputs (e.g. WTR-IM).
Selected transmitters
4
5
2
3
11
16
17
18
19
20
12
13
14
15
27
28
21
26
29
30
22
23
24
25
31
36
37
38
39
40
32
33
34
35
41
46
47
48
49
50
42
43
44
45
51
56
57
58
59
60
52
53
54
55
61
66
67
68
69
70
62
63
64
65
71
76
77
78
79
80
72
73
74
75
81
86
87
88
89
90
82
83
84
85
91
96
97
98
99
100
92
93
94
95
List of transmitters that are used in the average
group. The selected transmitters are marked with
green background and online transmitters are
marked with white background. Offline transmitters
can also be selected to the average group.
Temperature average
high cutoff
-100...100 °C
0,0 °C
Set the highest value that is used in the average
calculation. Values over the set value are not used
in the calculation. The parameter is available only
for temperature average groups.
Temperature average
low cutoff
-100...100 °C
0,0 °C
Set the lowest value that is used in the average
calculation. Values below the set value are not
used in the calculation. The parameter is available
only for temperature average groups.
4.2 Configuring alarms
1.
Press the
Alarm Settings
button in the
Configurations
view.
2.
Make the settings.
See the chapter
on page 22 for more details.
3.
Press the
Confirm changes
button to save the changes.
4.
Press
Install to device
button to write the changes to the device.
4.2.1 Available settings for alarms
Parameter name Values
Default
Description
Offline alarm
Off / 180...65535 s 7200 s
Alarm for offline transmitters. Set the offline time
that activates the alarm.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.