Published: 18.07.2019
42 (63)
Regis-
ter
Parameter description
Data type Values
Range
Default
2XX30
Scrolling value selection.
Unsigned 16 bits 0...15
0. Temperature
1. Humidity
2. Additional
measurement 1
(CO
2
)
3. Additional
measurement 2
4. Additional
measurement 3
5. Additional
measurement 4
6. External input 1
7. External input 2
8. External input 3
9. External input 4
10.I2C value 1
11.I2C value 2
12.I2C value 3
13.Value over bus 1
14.Value over bus 2
15.Value over bus 3
2
2XX31
Scrolling delay. Time to show each
value on display. Affects also to
display off delay. Display off delay
= (number of items in scrolling
value selection) * (display scrolling
delay).
Unsigned 16 1...30
1...30 s
10
2XX32
Not in use.
-
-
-
0
2XX33
Not in use.
-
-
-
0
2XX34
Not in use.
-
-
-
0
2XX35
Button function. The first press
activates the display if the display
is not on.
Unsigned 16 0 - 1 - 2
0. Manual value
scroll
1. Button function is
managed in base
unit
2. Extra time
function
0
2XX36
Not in use.
-
-
-
0
2XX37
Not in use.
-
-
-
0
Holding registers for transmitter measurement settings
Table reading instruction: The register numbers include an XX in the middle. Replace the XX with the
transmitter ID - 1 value. For example, a transmitter with the ID 6: XX = 05.
Regis-
ter
Parameter description
Data type Values
Range
Default
2XX38
External input 1.
Unsigned 16 0 - 1 - 2 - 3 - 4
- 5 - 6
0. Off
1. 0...10 V
2. 0...20 mA
3. Resistance x 0,1
4. Resistance x 10
5. NTC 10
6. Pt1000
0
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.
EN - 5401comm