Published: 18.07.2019
21 (63)
7.
Press the
Configure manually
button.
Configurations
view has the following menus:
Average groups
Set up average group calculations from measured values. There are five
calculation groups available.
Alarm Settings
Set up measurement alarms.
WTR Input Register
Cloning
Set up input register cloning.
Value Over Bus
Set up value over bus (VOB) settings.
Communication
Set up communication parameters. Also the basic wireless network settings can
be set via this menu.
See more information about the settings from the following chapters.
8.
Make the changes to configuration.
9.
Press
Install to device
button to write the changes to the device.
10.
Press the
Back
button.
11.
Press the
Back
button again to disconnect from the device.
12.
Select the disconnecting method.
• Select
Disconnect
to disconnect the device without deactivating the device Bluetooth.
• Select
End commissioning
to disconnect the device and deactivate the device Bluetooth.
Note:
The wireless network communication (MIRA communication) starts only if
the Bluetooth is deactivated. However, the device also deactivates the Bluetooth if
connection to Produal MyTool
®
is lost for 30 minutes.
4.1 Configuring average measurement groups
You can configure up to five average measurement groups. One transmitter can be in several groups
and one group can include only one measured property.
1.
Press the
Average Groups
button in the
Configurations
view.
2.
Select the group you are going to set by pressing the number.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.
EN - 5401comm