Published: 18.07.2019
29 (63)
Register Parameter description
Data type Values
Range
10301
Time that has elapsed since the transmitter
has been last seen on network, ID 2.
Unsigned 16 0...65535
0...65535 s
...
...
...
...
...
10399
Time that has elapsed since the transmitter
has been last seen on network, ID 100.
Unsigned 16 0...65535
0...65535 s
Input registers for network topology
Register Parameter description
Data type Values
Range
10400
Parent device ID for the device with ID 1.
Unsigned 16 0...100 / 255
0 = base unit,
ID 1...100, 255
= transmitter is
not connected to
network
10401
Parent device ID for the device with ID 2.
Unsigned 16 0...100 / 255
0 = base unit,
ID 1...100, 255
= transmitter is
not connected to
network
...
...
...
...
...
10499
Parent device ID for the device with ID 100.
Unsigned 16 0...100 / 255
0 = base unit,
ID 1...100, 255
= transmitter is
not connected to
network
Input registers for extreme measurement values
Register Parameter description
Data type Values
Range
12000
Lowest measured temperature value.
Signed 16
-1000...1000
-100,0...100,0 °C
12001
Device ID for the lowest measured
temperature value.
Unsigned 16 1...100
ID 1...100
12002
Register of the lowest measured temperature
value.
Unsigned 16 37...48
37...48
12003
Highest measured temperature value.
Signed 16
-1000...1000
-100,0...100,0 °C
12004
Device ID for the highest measured
temperature value.
Unsigned 16 1...100
ID 1...100
12005
Register of the highest measured temperature
value.
Unsigned 16 37...48
37...48
12006
Lowest measured humidity value.
Unsigned 16 0...10000
0...100,00 %rH
12007
Device ID for the lowest measured humidity
value.
Unsigned 16 1...100
ID 1...100
12008
Register of the lowest measured humidity
value.
Unsigned 16 37...48
37...48
12009
Highest measured humidity value.
Unsigned 16 0...10000
0...100,00 %rH
12010
Device ID for the highest measured humidity
value.
Unsigned 16 1...100
ID 1...100
12011
Register of the highest measured humidity
value.
Unsigned 16 37...48
37...48
12012
Lowest measured CO
2
value.
Unsigned 16 0...10000
0...10000 ppm
12013
Device ID for the lowest measured CO
2
value. Unsigned 16 1...100
ID 1...100
12014
Register of the lowest measured CO
2
value.
Unsigned 16 37...48
37...48
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]