PE6000 User Manual Description of Function Codes
161
Multi-reference can be switched over based on different states of DI terminals. For details, see
the descriptions of group F4.
Function
Code
Parameter Name
Setting Range
Default
PC-16
Simple PLC running
mode
0: Stop after the AC drive runs one cycle
1: Keep final values after the AC drive runs
one cycle
2: Repeat after the AC drive runs one cycle
0
Simple PLC can be either the frequency source or V/F separated voltage source.
When simple PLC is used as the frequency source, whether parameter values of PC-00 to
PC-15 are positive or negative determines the running direction. If the parameter values are
negative, it indicates that the AC drive runs in reverse direction.
Figure 5-31 Simple PLC when used as frequency source.
•
0: Stop after the AC drive runs one cycle
The AC drive stops after running one cycle, and will not start up until receiving another
command.
•
1: Keep final values after the AC drive runs one cycle
The AC drive keeps the final running frequency and direction after running one cycle.
•
2: Repeat after the AC drive runs one cycle
The AC drive automatically starts another cycle after running one cycle, and will not stop until
Running
direction
DO or relay
output
250 ms pulses
Time (t)