PE6000 User Manual Description of Function Codes
117
Value
Function
Range (Corresponding to Pulse or Analog
Output Range 0.0%–100.0%)
13
Motor rotational speed
0 to rotational speed corresponding to
maximum output frequency
14
Output current
0.0–1000.0 A
15
Output voltage
0.0–1000.0 V
16
Output torque (actual value)
-2 times of rated motor torque to 2 times of
rated motor torque
Function
Code
Parameter Name
Setting Range
Default
P5-09
Maximum FMP output frequency
0.01–100.00 kHz
50.00 kHz
If the FM terminal is used for pulse output, this parameter is used to set the maximum
frequency of pulse output.
Function
Code
Parameter Name
Setting Range
Default
P5-10
AO1 offset coefficient
-100.0%–100.0%
0.0%
P5-11
AO1 gain
-10.00–10.00
1.00
These parameters are used to correct the zero drift of analog output and the output amplitude
deviation. They can also be used to define the desired AO curve.
If "b" represents zero offset, "k" represents gain, "Y" represents actual output, and "X"
represents standard output, the actual output is: Y = kX + b.
The zero offset coefficient 100% of AO1 and AO2 corresponds to 10 V (or 20mA). The
standard output refers to the value corresponding to the analog output of 0 to 10 V (or 0 to 20mA)
with no zero offset or gain adjustment.
For example, if the analog output is used as the running frequency, and it is expected that the
output is 8 V when the frequency is 0 and 3 V at the maximum frequency, the gain shall be set to
-0.50, and the zero offset shall be set to 80%.
Function
Code
Parameter Name
Setting Range
Default
P5-17
FMR output delay time
0.0–3600.0s
0.0s
P5-18
Relay 1 output close delay time
0.0–3600.0s
0.0s
P5-19
Relay 1 output open delay time
0.0–3600.0s
0.0s
P5-20
DO1 output delay time
0.0–3600.0s
0.0s