PE6000 User Manual Description of Function Codes
133
P8-20
Frequency detection
hysteresis (FDT hysteresis 1)
Default
5.0%
Setting Range
0.0%–100.0% (FDT1 level)
If the running frequency is higher than the value of P8-19, the corresponding DO terminal
becomes ON. If the running frequency is lower than value of P8-19, the DO terminal goes OFF
These two parameters are respectively used to set the detection value of output frequency and
hysteresis value upon cancellation of the output. The value of P8-20 is a percentage of the
hysteresis frequency to the frequency detection value (P8-19). The FDT function is shown in the
following figure.
Figure 5-16 FDT level
P8-21
Detection range of frequency
reached
Default
0.0%
Setting Range
0.00–100% (maximum frequency)