PE6000 User Manual Description of Function Codes
127
Function
Code
Parameter Name
Setting Range
Default
P7-09
Accumulative running time
0–65535 h
0h
It is used to display the accumulative running time of the AC drive. After the accumulative
running time reaches the value set in P8-17, the terminal with the digital output function 12
becomes ON.
Function
Code
Parameter Name
Setting Range
Default
P7-10
Countdown started for stop
0
:
Stop
1
:
Start
0
P7-11
Preset value for timing stop
0-65535
0
P7-12
Number of decimal places for load speed
display
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
0
P7-08,P7-10, P7-11 It is used for
passwords for timing stop
.
If P7-08 is set to any non-zero number, the password protection function is enabled. After
a
password has been set and taken effect, you must enter the correct password in order to
enter the menu. If the entered password is incorrect you cannot view or modify parameters.
If F7-08 is set to 00000, the previously set user password is cleared, and the password
protection function is disabled.
Ÿ
P7-10 = 1,starting the
Timer, until the P7-11 countdown to 0
.
Ÿ
P7-10 = 0, disable this
countdown timer
.
P7-12 is used to set the number of decimal places for load speed display. The following
gives an example to explain how to calculate the load speed:
Assume that P7-06 (Load speed display coefficient) is 2.000 and P7-12 is 2 (2 decimal
places). When the running frequency of the AC drive is 40.00 Hz, the load speed is 40.00
x2.000=80.00 (display of 2 decimal places).
If the AC drive is in the stop state, the load speed is the speed corresponding to the set
frequency, namely, "set load speed". If the set frequency is 50.00 Hz, the load speed in the stop