PE6000 User Manual Operation, Display and Application Examples
17
Figure
3
-2 Operation procedure on the operation panel
You can return to Level II menu from Level III menu by pressing PRG or ENTER. After you
press ENTER, the system saves the parameter setting first, and then goes back to Level II menu
and shifts to the next function code. After you press PRG, the system does not save the parameter
setting, but directly returns to Level II menu and remains at the current function code.
Here is an example of changing the value of P3-02 to 15.00 Hz
Figure 3-3 Example of changing the parameter value
In Level III menu, if the parameter has no blinking digit, it means that the parameter cannot be
modified. This may be because:
1)
Such a function code is only readable, such as, AC drive model, actually detected
parameter and running record parameter.
2)
Such a function code cannot be modified in the running state and can only be changed at
stop.
Status parameter
(Default display)
Level-I menu
(Select the function code group)
Level- II menu
(Select the function code)
Switch
Level- III menu
(Set the value of the function code)
BACK
Cancel
If there is a blinking digit, press
△
/
/
to modify the digit
BACK
Next function
code