PE6000 User Manual Description of Function Codes
173
A6-06
AI curve 4 maximum input
Default
10.00 V
Setting Range
A6-06 to 10.00 V
A6-07
Corresponding setting of AI curve 4
maximum input
Default
100.0%
Setting Range
-100.0%–100.0%
A6-08
AI curve 5 minimum input
Default
0.00 V
Setting Range
-10.00 V to A6-10
A6-09
Corresponding setting of AI curve 5
minimum input
Default
0.0%
Setting Range
-100.0%–100.0%
A6-10
AI curve 5 inflexion 1 input
Default
3.00 V
Setting Range
A6-08 to A6-12
A6-11
Corresponding setting of AI curve 5
inflexion 1 input
Default
30.0%
Setting Range
-100.0%–100.0%
A6-12
AI curve 5 inflexion 1 input
Default
6.00 V
Setting Range
A6-10 to A6-14
A6-13
Corresponding setting of AI curve 5
inflexion 1 input
Default
60.0%
Setting Range
-100.0%–100.0%
A6-14
AI curve 5 maximum input
Default
10.00 V
Setting Range
A6-14 to 10.00 V
A6-15
Corresponding setting of AI curve 5
maximum input
Default
100.0%
Setting Range
-100.0%–100.0%
The function of curve 4 and curve 5 is similar to that curve 1 to curve 3, but curve 1 to curve 3
are lines, and curve 4 and curve 5 are 4-point curves, implementing more flexible corresponding
relationship. The schematic diagram of curve 4 and curve 5 is shown in the following figure.