Description of Function Codes PE6000 User Manual
116
Value
Function
Description
37
Frequency lower limit
reached (having
output at stop)
If the running frequency reaches the lower limit, the
terminal becomes ON. In the stop state, the signal is still
ON.
38
Alarm output
If a fault occurs on the AC drive and the AC drive
continues to run, the terminal outputs the alarm signal.
40
Current running time
reached
If the current running time of AC drive exceeds the value
of 8-53, the terminal becomes ON.
41
Fault Output
Fault output is the fault of coasting to stop and no output
in occasion of under voltage.
Function
Code
Parameter Name
Default
P5-06
FMP function selection
0
P5-07
AO1 function selection
0
The output pulse frequency of the FMP terminal ranges from 0.01 kHz to "Maximum FMP
output frequency" (P5-09). The value of P5-09 is between 0.01 kHz and 100.00 kHz.
The output range of AO1 and AO2 is 0–10 V or 0–20 mA. The relationship between pulse and
analog output ranges and corresponding functions is listed in the following table.
Table Relationship between pulse and analog output ranges and corresponding functions
Value
Function
Range (Corresponding to Pulse or Analog
Output Range 0.0%–100.0%)
0
Running frequency
0 to maximum output frequency
1
Set frequency
0 to maximum output frequency
2
Output current
0 to 2 times of rated motor current
3
Output torque (absolute value)
0 to 2 times of rated motor torque
4
Output power
0 to 2 times of rated power
5
Output voltage
0 to 1.2 times of rated AC drive voltage
6
Pulse input
0.01–100.00 kHz
7
AI1
0–10 V
8
AI2
0–10 V (or 0–20mA)
11
Count value
0 to maximum count value
12
Communication setting
0.0%–100.0%