Description of Function Codes PE6000 User Manual
112
the corresponding curve of AI1, AI2 and AI3. Any of the five curves can be selected for AI1, AI2 and
AI3.
Curve 1, curve 2 and curve 3 are all 2-point curves, set in group F4. Curve 4 and curve 5 are
both 4-point curves, set in group A6.
The PE6000 provides two AI terminals as standard.
Function
Code
Parameter Name
Setting Range
Default
P4-34
Setting for AI less than
minimum input
Unit's digit (Setting for AI1 less than
minimum input)
00
0: Minimum value
1: 0.0%
Ten's digit (Setting for AI2 less than
minimum input)
0, 1 (same as AI1)
Hundred's digit (Setting for AI3 less than
minimum input)
Reserved
This parameter is used to determine the corresponding setting when the analog input voltage is
less than the minimum value. The unit's digit, ten's digit and hundred's digit of this parameter
respectively correspond to the setting for AI2, AI2 and Reserved.
If the value of a certain digit is 0, when analog input voltage is less than the minimum input, the
corresponding setting of the minimum input (P4-14, P4-19, P4-24) is used.
If the value of a certain digit is 1, when analog input voltage is less than the minimum input, the
corresponding value of this analog input is 0.0%.
Function
Code
Parameter Name
Setting Range
Default
P4-35
DI1 delay time
0.0–3600.0s
0.0s
P4-36
DI2 delay time
0.0–3600.0s
0.0s
P4-37
DI3 delay time
0.0–3600.0s
0.0s
These parameters are used to set the delay time of the AC drive when the status of DI
terminals changes.
Currently, only DI1, DI2 and DI3 support the delay time function.