Function description
Operating Manual PSENvip R, PSENvip R LR,PSENvip E
1003449-EN-06
| 53
4.9.1
System cycle for standard press stroke
PSENvip transfers position values to the special module PSSu K F FAU P (see I/O data
type PROTECTION_FIELD_SIZE), which can be used in the user program for feasibility
testing.
A press stroke with full protected field has the following states:
}
Press is at top dead centre
Protected field: Free
Dynamic muting: Inactive
Position = Protected field height (including r advance measuring field)
Position =
<Configured overrun>
+ 6 mm + 2 mm
Signal/action
Status
Press
Foot switch
0
v = 0
TDC
System-Init
1
OSSD
1
Mute
1
Muting OSSD
Inactive
Monitoring of braking ramp
Inactive
Monitoring of pinch point
Inactive
}
Downward movement (rapid traverse)
Protected field: Free
Dynamic muting: Inactive
Position = Protected field height (including r advance measuring field)
Position =
<Configured overrun>
+ 6 mm + 2 mm
Signal/action
Status
Press
Foot switch
1
v > 0
System-Init
0
OSSD
1
Mute
1
Muting OSSD
Inactive
Monitoring of braking ramp
Inactive
Monitoring of pinch point
Inactive
}
Downward movement, advance measuring field touches workpiece at the pinch
point (KP)