Attachment
13.1
Check list
The following check list is intended as a guide to provide support when commissioning and
recommissioning the PSENvip and when carrying out the regular inspection as required.
Please note that the check list is not intended to replace the plant-specific safety analysis
required for commissioning/recommissioning, nor the resulting inspections and actions.
INFORMATION
Commissioning, recommissioning and regular inspection may only be car-
ried out by competent personnel.
We recommend that you keep the completed check list and store it with the machine docu-
mentation for reference.
No
.
Action
OK
Not
OK
Notes
1
Check the category/standards
Does the category of the PSENvip match the cat-
egory required for the plant/machine?
Have the standards applicable for the plant/ma-
chine been considered?
2
Check the ambient conditions for PSENvip
Are the technical details of the PSENvip complied
with?
3
Check the wiring of the PSENvip
Are all the electrical connections to the PSENvip
wired correctly?
Do the power supply for generating the 24 V supply
voltage and the voltages to the inputs on the PSEN-
vip comply with the regulations for safe electrical
isolation?
Are the cables adequately shielded?
4
Visual inspection
Make sure that there are no objects in the protected
space between the transmitter and receiver.
Make sure that there are no transparent materials
between the transmitter and receiver (e.g. glass
panel).
Are all the mechanical connections to the
PSENvip attached correctly?
Cables are undamaged?