OPERATING AND INSTALLATION INSTRUCTIONS LBE 250 / LBE 500
PAGE 14
8.3 SETTINGS
• With the
Temperature
parameter, the air temperature at
the outlet of the air humidification unit is set between 15
°C and 25 °C in one degree intervals. A value of 21 °C is
preset at the factory.
• With the
TemperatureE
parameter (E = external tempe-
rature sensor), the desired air temperature at the exter-
nal sensor is set between 15 °C and 25 °C in one degree
intervals.
• With the
Humidity parameter
, the desired outlet humi-
dity is set between 40 % and 60 % relative humidity at
five percent intervals. A value of 50 % relative humidity is
preset at the factory.
• In the
Service
menu item, information regarding the ope-
rational status is displayed.
• Internal Sensor
shows the currently measured air tem-
perature and the relative humidity at the air outlet of the
air humidification unit.
• External Sensor
indicates the currently measured air
temperature at the external temperature sensor.
• If a sensor is not connected, the Ext. Sensor display is not
connected!
• The installed software version is shown under
Info
.
• Error messages, which appear in the Info line of the dis-
play, are deleted using the
Delete Fault Yes<
function.
• With
Expert
, you can access the next lower menu level by
entering a code. This parameter can be opened only by
the respective expert.
9. Operational statuses
9.1 AUTOMATIC ACTIVATION/DEACTIVATION AUTUMN/SPRING (AUTO STANDBY)
• The air humidification unit switches on when the air hu-
midity is too low (Autumn) and off when the air humidity
is too high (Spring). The following appears on the dis-
play:
auto STANDBY
.
• If the evaporative power within 24 hours is less than one
litre, the device switches off (auto STANDBY).
• If the humidity undershoots the set humidity by 7 % for
a period of 24 hours, the air humidification unit switches
on again.
a
uto S
TANDBY
CONTROL ON
US
ER
G
ENER
A
L
S
PE
CI
A
LI
S
T PER
S
O
NNEL
Temperature 21°C <
Humidity
50 % <
Service <
Internal Sensor <
Temperature
21 °C
Humidity 50 %
External Sensor <
Ext. Sensor 21 °C
g
Ext. Sensor display is not connected!
Info
<
V 1.0
Software Version
01.09.08
Delete Fault <
Delete
Yes<
Fault?
No
Expert
<
Code?
------