OPERATING AND INSTALLATION INSTRUCTIONS LBE 250 / LBE 500
PAGE 28
For mounting and setup, the national
and local regulations must be obser-
ved. The device may be installed only in
compliance with the national installation
regulations.
The device may be installed only in
frost-free, dry rooms. The room tem-
perature must lie b5 °C and
a maximum of +40 °C. The device is
intended for horizontal mounting. It may
deviate a max/-1° from the
horizontal position and must be mounted
to a massive wall that can bear the load.
Theintrinsic operating weight of the air
humidification unit must be taken into
consideration for the suspension. No
shocks or jolts may affect the device.
The installation of the air humidification
unit may take place only in rooms that
have an existing water outlet.
In addition, safety measu-
res that automatically close
the water supply to the air
humidification unit in case of leakage
(e.g. safety valve/water stop) must be
taken within the room. Ventilation and
air conditioning system air lines that are
not installed in heated areas must be
designed with suitable heat insulation
(danger when the dew point temperature
is undershot) to prevent the formation of
condensation.
The setup site for the air humidification
unit must be easily accessible for main-
tenance and servicing work.
A
minimum spacing of 20 cm
(LBE 250) / 25 cm (LBE 500)
must be maintained above the
air humidifier.
A minimum spacing of 25
cm (LBE 250 / LBE 500)
must be main-
tained below the air humidifier.
During the installation of the ventilation
lines, make sure that no
metal chips
get
into the pipework (metal chips cause
corrosion points in the water tank). After
the air lines have been cut to size and
mounting is completed, the air lines
should be thoroughly cleaned.
For any damage due to non-observance
of this information, the warranty extin-
guishes.
Attach the wall mounting bracket
ho-
rizontally
(max. dev/-1°) using
fastening screws and dowels with at
least ø 6 mm to a massive wall that can
bear the load.
Hang the air humidification unit into the
wall mounting bracket and secure it to
the device with both lateral
screws
.
16. Mounting
Minimum distance for installation
with the closed unit:
20 cm distance LBE 250, top
25 cm distance LBE 250, bottom
25 cm distance LBE 500, top and bottom