OPERATING AND INSTALLATION INSTRUCTIONS LBE 250 / LBE 500
PAGE 25
14. Technical data
Version
LBE 250
LBE 500
Air volume flow
[m³/h]
max. 250
max. 500
Humidity, adjustable
[%]
40 to 60
40 to 60
Temperature, adjustable
[°C]
15 to 25
15 to 25
Evaporative power
[l/h]
max. 2
max. 4
Water replacement
[l/day]
(depends on water hardness and evaporative power)
1 to 10
2 to 30
Pressure dropt
[Pa]
max. 80
max. 30
Power consumption
[W]
max. 100
max. 100
on average
[W]
(design option with water heater batteries)
23
23
Power consumption
[W]
(design option with electric heater batteries)
max. 1400
–
Power supply
[V/Hz]
230/50
230/50
Connection to air supply
[mm]
ø 160
ø 250
Connection to water supply
[Zoll]
ø ¾
ø ¾
Connection to drain
[mm]
ø 40
ø 40
Siphon
provided by client
provided by client
Water inlet pressure
[MPa]
min/max. 0,35/0,7
min/max. 0,35/0,7
Water temperature
[°C]
min/max. 8/30
min/max. 8/30
Weight (without/with water)
[kg]
25/28
46/61
Protection rating for
[IP]
20
20
Installation
wall mounting
wall mounting
Hygiene – Type Examination
(Hygiene-Institut des Ruhrgebiets)
PTC Electric Heater Battery
Heat output PTC element
[W]
1300
–
Water heater battery
Medium
water
water
Temperature supply line, return line
[°C]
55/45
55/45
Performance
[W]
2000
4200
Air inlet
[°C]
15
15
Air outlet
[°C]
40
40
Water quantity
[l/s]
0,05
0,13
Connection (copper pipe)
[mm]
ø 10
ø 22
Water pressure
[MPa]
max. 1
max. 1
Water temperature
[°C]
max. 95
max. 95
US
ER
G
ENER
A
L
S
PE
CI
A
LI
S
T PER
S
O
NNEL