58
Bit
Name
Meaning
I11.4
Invalid con-
trol value
is set if an invalid control value is set in the control data,
e.g. too high a frequency for free run.
I11.5
Invalid OP
mode
(operating
command)
is set if an invalid value for the motion command is set in
the control data.
I11.6
Invalid
feedback
operating
mode
is set if an invalid value for the feedback operating mode
is set in the control data.
I11.7
READY
is set when the module is ready to accept a new operat-
ing command.
7.3 Data Record Transfer
All parameters of the data record 128 (DS128) are preset by the configuration.
The complete data record of the power stage can also be transferred in the run-time to the
TM StepDrive technology module.
The parameters are changed by the mechanism "Read / write data record
“. In TIA Portal
®
the system functions WRREC
(write data record) and
RDREC
(read data record) are
available.
.
i
If the "run frequency" or "acceleration and deceleration" parameters are
written while a " Move to absolute position" or " Move a relative distance"
motion command is running, the parameters are not accepted until the
positioning is completed. Reading back from the module is possible at any
time.
Data records 128 and 245 are described in table form in chapter 12.
i
The data record can be read
without
restriction.
Содержание TM StepDrive 1x24..48V/5A
Страница 11: ...Technology Module TM StepDrive 1x24 48V 5A MA 1303 A007 EN 10 1 5 Declaration of Conformity...
Страница 51: ...Technology Module TM StepDrive 1x24 48V 5A MA 1303 A007 EN 50...
Страница 77: ...Technology Module TM StepDrive 1x24 48V 5A MA 1303 A007 EN 76...
Страница 92: ...Phytron GmbH Industriestra e 12 82194 Gr benzell T 49 8142 503 0 F 49 8142 503 190 www phytron eu...