phytron
57
MA 1303-A007 EN
Bit
Name
Meaning
I10.0
Rotation
is set, if the motor rotates in negative direction.
I10.2
Hardware
limit switch
active
is set, when an input parameterised as a limit switch be-
comes active for a traversing job.
I10.3
Software
limit switch
active
is set, when, for a traversing job, the distance is exceeded
via the parameterised value of the distance limitation.
I10.4
limit switch
error
is set if the parameterisation of the limit switches is incor-
rect, e.g. if two switches have been assigned the identical
function.
I10.5
Internal error is set, when the module is malfunctioning or defective.
I10.6
Power stage
error
is set, when one of the following errors occurs, which
switched off the power stage for self-protection: undervolt-
age detected, exceed temperature of 105 °C.
I10.7
Positioning
error
is set,
- if a software or hardware limit switch is crossed dur-
ing positioning, or
- if a switch was not found within the distance limit
during referencing, or
- if the wrong limit switch was activated during refer-
encing.
If the error occurs during referencing, the
"Error limit
switch"
bit is also set.
I11.0
Warning
temperature
is activated when the board temperature is higher than
85 °C and
is deleted when the temperature is lower.
I11.1
Shutdown
temperature
is set when the board temperature has reached over
105 °C and must be deleted by the user program (control
bit error reset).
I11.2
No load volt-
age
is set when the load voltage is missing and is deleted
again when it is applied again.
I11.3
DIS input
active
Is set, when the "DIS" input is activated.
Содержание TM StepDrive 1x24..48V/5A
Страница 11: ...Technology Module TM StepDrive 1x24 48V 5A MA 1303 A007 EN 10 1 5 Declaration of Conformity...
Страница 51: ...Technology Module TM StepDrive 1x24 48V 5A MA 1303 A007 EN 50...
Страница 77: ...Technology Module TM StepDrive 1x24 48V 5A MA 1303 A007 EN 76...
Страница 92: ...Phytron GmbH Industriestra e 12 82194 Gr benzell T 49 8142 503 0 F 49 8142 503 190 www phytron eu...