Operation and maintenance
Starting and stopping
DK9401A1
www.pelltech.eu
Note:
Comma “,” is used as decimal separator.
Table 2 Info menu description
Screen text
Description
Pwr 00/550 kW
Current and maximum power. Max power can be changed from main menu.
Tstn=181
0
C T1=2685
0
C
Tstn – fire brick temperature, T1 - PT
Fan=10/13±2 14/15
10 – primary fan actual speed, 13 – primary fan setpoint speed. Actual speed is
controlled to match setpoint speed. ±2 - Base air value. Controller tries to keep
speed se base air. In this case controller keeps speed 15rps. Speed unit is
rps (revolutions per second).
14/15 – same as above for secondary fan. Base air setting is same ±2
Δp=-0,2/-15Pa
Burning chamber pressure value. -0,2 is current measured pressure and -15 is
setpoint. Controller regulates flue gas fan speed to keep this pressure. Depends
also on PAR60 value.
Total=10 kg
Roughly the amount of pellets burnt. It is measured by counting internal feeder
rotations. Number is reset by firmware upgrade
Count=12,1 kg 180/254
Roughly the amount of pellets burnt, resettable by user.
U=25V68 I=0.0A
U - DC power voltage 25V68 means 25.68V. I – Feeders and/or grate motor
current
Ver=2.02c 19/12/12
Firmware version and date
4.2 Starting and stopping
To turn on the burner, switch on boiler main switch. If burner displays ’Stopped’, then go to STATUS
menu and change parameter ’Burner’ from ON to OFF. The display shows ’Waiting’. Now turn boiler
thermostat to desired temperature. The burner will go to Loading-state. If this is the first run, external
auger needs to fill up with pellets. It can take as long as 20minutes.
4.3 Statuses and parameters
PV1000agri pellet burner operates in many different states, which are called “Status”. Current and
previous statuses can be seen from user interface panel (chapter 4.1). Burner changes its status based
on input signals from sensors and user. Below are given the statuses in order of typical working cycle.
Table 3 Summary of burner statuses
Status
Short description
Waiting
Waiting signal from boiler thermostat
Testing
Thermostat is switched on, testing battery, fans, feeder, level sensors, draft
Cleaning
Ash removing from burning chamber
Loading
Loading pellets with auger into burner and by feeder into burning chamber
Igniting
Igniter is turned on, pellets igniting
Pre-burn
Flame is recognized, small amount of pellets is added by feeder
Heat up
Burning chamber Ceramic is heated up
Burning
Normal burning operation
Hold flame
Thermostat is switched off, small flame is held alive
End burn
Thermostat is switched off, feeder is cleaned up
Содержание PV1000agri
Страница 1: ...PV1000agri pellet burner User manual POOLELI DRAFT DK9401A1 ...
Страница 24: ...PV1000agri pellet burner p 23 50 Installation Electrical connections DK9401A1 www pelltech eu ...
Страница 25: ...PV1000agri pellet burner p 24 50 Installation Electrical connections DK9401A1 www pelltech eu ...
Страница 26: ...PV1000agri pellet burner p 25 50 Installation Electrical connections DK9401A1 www pelltech eu ...
Страница 39: ...PV1000agri pellet burner p 38 50 Operation and maintenance Replacing components DK9401A1 www pelltech eu ...