PV1000agri pellet burner
p
47/ 50
Annex B – Burner status change logic
DK9401A1
www.pelltech.eu
Burn end
End blow
Burn end (15*rot. + 10rot.) plus time 30sec. is reached
Burning
Signal from boiler Thermostat, feeder made less than 8 rot and
previous state was BURN
End Blow
Waiting
No Flame 1 min. and RUN command is active
Stopped
No Flame 1 min. and RUN command is NOT active
No flame
Max cleaning time (5 min.) is reached
Level error
No Flame 1 min. and error is set From: Burn-> Burn end-> End blow-
>Level error
No pellets
No Flame 1 min. and error is set From: Burn-> Burn end\-> End blow-
>No pellets
No Power
Wait
Power exist and RUN command is active
Stopped
Power exist and RUN command is NOT active
Burning
If Burned before No Power and less than 15 min in No Power
Any other
Waiting
RUN command is activated