![Parker Compax3S025V2 Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/parker/compax3s025v2/compax3s025v2_operating-instructions-manual_3903775035.webp)
Parker EME
Compax3 device description
192-120101 N11 C3I11T11 November 2007
35
3.4.2.
Connections on the device bottom
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after
switching off the power supply!
Caution!
When the control voltage is missing there is no indication whether or
not high voltage supply is available.
PE connection
The PE connection is made with 10mm
2
via a grounding screw at the
bottom of the device.
Attention hot surface!
The heat dissipator can reach very high temperatures (>70°C)
MP
Power module
X40 Braking
Resistor
X41 Mains
supply
VAC/PE
1
Central ground connection for the axis combination,
with 10mm
2
to the ground screw on the housing.
4 Fan*
M
Axis controller
X43
Motor / Brake
2
Fixing for motor shield clamp
4 Fan*
3
optinally, the axis controller features a ground screw
on the housing, if the grounding is not possible via the
back plate.
* is internally supplied.
Line cross-sections of the power connections (on the device bottoms)
Compax3 device:
Cross-section: Minimum... Maximum[mm
2
with contactor
sleeve]
M050, M100, M150
0,25 ... 4 (AWG: 23 ... 11)
MP10
Mains supply: 0,5 ... 6 (AWG: 20 ... 10)
Braking resistor: 0,25 ... 4 (AWG: 23 ... 11)