Technical
data
Positioning via digital I/Os
296
192-120101 N11 C3I11T11 November 2007
Control voltage 24VDC Compax3S and Compax3H
Controller type
Compax3
Voltage range
21 - 27VDC
Mains module
with switch-on current limitation, due to
capacitive load
Fuse
MTP miniature circuit breaker or "delayed action
fuse", due to capacitive load
Current drain of the device
0.8A
Total current drain
0.8 A + Total load of the digital o
current for the motor holding brake
Ripple
0.5Vpp
Requirement according to safe extra
low voltage (SELV)
yes
Short-circuit proof
conditional (internally protected with 3.15AT)
Control voltage 24VDC Compax3MP / Compax3M
Device type
Compax3MP / Compax3M
Voltage range
21 - 27VDC
Mains module
with switch-on current limitation, due to
capacitive load
Fuse
MTP miniature circuit breaker or "delayed action
fuse", due to capacitive load
Current drain of the device
C3MP10D6: 0.2A
Total current drain
C3M050D6: 0.85A
C3M100D6: 0.85A
C3M150D6: 0.85A
+ Total load of the digital o current for
the motor holding brake
Ripple
0.5Vpp
Requirement according to safe extra
low voltage (SELV)
yes
Short-circuit proof
conditional (internally protected with 3.15AT)
Output data Compax3S0xx at 1*230VAC/240VAC
Controller type
S025V2
S063V2
Output voltage
3x 0-240V
3x 0-240V
Nominal output current
2.5Aeff 6.3Aeff
Pulse current for 5s
5.5Aeff 12.6Aeff
Power
1kVA 2.5kVA
Switching frequency
16kHz 16kHz
Power loss for In
30W 60W
Output data Compax3S1xx at 3*230VAC/240VAC
Controller type
S100V2
S150V2
Output voltage
3x 0-240V
3x 0-240V
Nominal output current
10Aeff
15Aeff
Pulse current for 5s
20Aeff 30Aeff
Power
4kVA 6kVA
Switching frequency
16kHz 8kHz
Power loss for In
80 W
130W