PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
52
System will automatically go into Maintenance Mode and stay in this mode until the
firmware update is complete. When the system goes into Maintenance Mode, the
system will have an audio beep every 15 seconds. Refer to Identifying Maintenance
Mode for characteristics of the system during Maintenance Mode. This check box will
allow the customer to prevent the system from sounding the audio beep every 15
seconds during firmware update.
Start TFTP Download… Button
Clicking on this button will cause the PViQ™ Connectivity System to transition into
Maintenance Mode and start the firmware update on the system. A valid TFTP server
address must be in the Server Address field and a valid firmware update filename must
be in the
FW Filename
fields in the TFTP Download Server section on this page to
allow the firmware update to be successful.
Update Status
This is a read-only field that is automatically updated as the status changes during a
firmware update to the PViQ™ Connectivity System.
Error Status
This is a read-only field that is automatically updated if any errors occur during a
firmware update to the PViQ™ Connectivity System.
Network Time Protocol (NTP)
This section provides the controls for connecting and setting up a Network Time
Protocol (NTP) server on the PViQ™ Connectivity System. This system does not have a
battery to maintain real time. Connecting the system to an NTP server will guarantee
that that the PViQ™ Connectivity System will be on local real time and provide
meaningful timestamps on the alarm logs in the Logs Page.
Enable
Checking this box will enable the system to be connected to an NTP server. This is
required for meaningful timestamps on the log and email alerts.
Primary IP
This is a user-changeable field that allows the customer to enter the IP address of the
Primary NTP server that that they want the PViQ™ Connectivity System to get the time
from. If connection to this server fails, the system will attempt to get the time from the
Secondary (back up) NTP server.