PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
155
Entering Maintenance Mode
To Initialize Ports on the PViQ™ Connectivity System in Maintenance Mode:
1.
Press and hold both Function Keys on the PM Interface Unit for about 5 seconds.
NOTE: Only the PM panel/tray can initiate Maintenance Mode for the PViQ™
Connectivity System. The EM panels/trays cannot enter Maintenance Mode
without the PM.
Result: The panel will beep once when the keys are initially pushed and again
after 2 seconds. After 5 seconds, the Mode LED will blink green, indicating that
the panel has recognized the request to enter Maintenance Mode.
If the “Mode” LED does not blink green after five seconds, check the following:
• Ensure the Interface Unit is for a PM and not an EM
• Ensure the unit is getting power
• Ensure the PM module is fully inserted into the PViQ™ Connectivity
Panel/Tray
2.
Release both Function Keys simultaneously.
Result: The Mode LED will continue to flash for another 5 seconds, during which
time the user can confirm or cancel the Maintenance Mode.
3.
To
confirm
: press and release the left Function Key. The confirmation is
acknowledged with a beep.
To
cancel
: press and release the right Function Key or let the panel simply time
out after 5 seconds. The time out will be acknowledged by three short beeps.
After confirmation of Maintenance Mode, the PM and all connected EM Interface Unit
Mode LEDs will turn off and the MAC and TRC (Trace) LEDs will turn on. Additionally,
all port LEDs will turn red.
Figure 117: IU Maintenance Mode