![Panduit Smartzone PViQ Connectivity System Скачать руководство пользователя страница 157](http://html1.mh-extra.com/html/panduit/smartzone-pviq-connectivity-system/smartzone-pviq-connectivity-system_user-manual_3458906157.webp)
PVIQ™ CONNECTIVITY SYSTEM USER MANUAL V 1.0
156
The Maintenance Mode has a default 30-minute time limit before it will exit. Five
minutes before this time limit is reached, the panel will begin producing 2 short beeps
every 5 seconds, serving as a pre-timeout warning.
At any point after these warnings begin, the Maintenance Mode time can be extended
for an additional 30 minutes by pressing and releasing the left Function Key,
acknowledged by a beep to confirm the request.
NOTE: While in Maintenance Mode, the panel will produce a short beep every 15
seconds. By default, the PM and all connected EM Interface Unit MAC, Trace, and Sys
LEDs will be green, and all port LEDs will be red.
Maintenance Mode Resets
There are eight levels of initialization and resets that can be performed when the PM is
in Maintenance Mode:
• Level 1 – Reset the PViQ™ Connectivity System host processor (or exit
maintenance mode)
• Level 2 – Reset all non-host processors
• Level 3 – Performs Level 1 and Level 2 resets together
• Level 4 – Set IP configuration to DHCP (factory default)
• Level 5 – Clear SNMP community string, SNMP credentials and login
credentials to the factory default
• Level 6* – Clear the internal PViQ™ Connectivity System database to the
factory default, followed by a Level 3 reset
• Level 7* – Reformat the entire file system, including clearing the database,
followed by a Level 3 reset
• Level 8* – Reset firmware image to factory default, followed by a Level 7
reset. All firmware upgrades performed since installation will be lost.
*
WARNING
: Only qualified technicians should perform these resets. Level 6, 7 and 8
resets will cause the PViQ™ Connectivity System database to be cleared, losing all
current configurations, provisioning and patch field connectivity data. A Level 8 reset will
clear all data and reset the PViQ™ Connectivity System components to the factory
image and default database settings. A full firmware update is required after a Level 8
reset.