5. ELECTRICAL
WIRING
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely
following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each unit
and a circuit breaker for overcurrent protection should be
provided in the exclusive line.
(3) To prevent possible hazards from insulation failure, the unit
must be grounded.
(4) Each wiring connection must be done in accordance with
the wiring system diagram. Wrong wiring may cause the
unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very
dangerous. The manufacturer will accept no responsibility
for any damage or misoperation that occurs as a result of
such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant
rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as follows:
●
The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
●
Use shielded wires for inter-unit control wiring between units
and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop designated by the
manufacturer, because special-purpose tools are required.
5-2. Recommended Wire Length and Wire Diameter
for Power Supply System
Outdoor unit (3-phase)
(A) Power supply
Time delay
fuse or circuit
capacity
Wire size
Max. length
U-200PE1E8
14 mm
2
116 m
15 A
U-250PE1E8
14 mm
2
96 m
20 A
Indoor unit
Type
(B) Power supply
Time delay fuse or
circuit capacity
2.5 mm
2
E1
Max. 50/30 m
10/16 A
Control wiring
(C) Inter-unit (between outdoor
and indoor units) control wiring
(D) Remote control wiring
0.75 mm
2
(AWG #18)
Use shielded wiring*
1
0.75 mm
2
(AWG #18)
Max. 1,000 m
Max. 500 m*
2
N OT E
*1
With ring-type wire terminal.
*2
When the type “E1” is used with maximum length of 500 m
for group control, and if the remote controller for the group
control is wireless, the maximum length will be 400 m.
5-3. Wiring System Diagrams
(Example for 3-phase outdoor unit)
L2
L1
U2
U1
L3
N
A
L1
L2
L3
N
U2
U1
L
N
1
2
2
1
D
B
L
N
2
1
C
L
N
U1
U2
R1
R2
L1
L2
L3
N
N OT E
(1) Refer to Section 5-2. “Recommended Wire Length
and Wire Diameter for Power Supply System” for the
explanation of “A”, “B” and “C” in the above diagrams.
(2) The basic connection diagram of the indoor unit shows
the 7P terminal board, so the terminal boards in your
equipment may differ from the diagram.
(3) Refrigerant Circuit (R.C.) address should be set before
turning the power on.
Indoor Unit
7P terminal board
Outdoor Unit
5P terminal board
2P terminal board
Power
supply
Power
supply
Remote
controller
line
Unit
control
wiring
Unit Control
Line
E1 Type
Power supply*
220 – 240 V ~50/60 Hz
Remote
controller
WHT
BLK
* Regarding S-250PE1E8, the power supply is 220-240V, 50Hz only.
Ground
Ground
Ground
Outdoor unit (3-phase)
INV unit
Power supply
380 – 415 V, 3N, ~ 50/60 Hz
Indoor
unit
Big̲PAC̲eng.indb 13
2011/02/23 13:37:50
14
CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P Black,
location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.
(When shipping: In shorted condition.)
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)
Fig. 5-1
(3) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, otherwise misoperation from noise
my occur. (Fig. 5-2)
Connect wiring as shown in Section “5-3. Wiring System Diagram.”
Fig. 5-2
(4) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR) rating
specifications) or use the cables based on IEC standard. (245 IEC57, 245 IEC66)
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist.
Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire
securely with the fixing screw of the terminal plate.
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Prohibited
Prohibited
Indoor unit
Shielded wire
Ground
Ground
How to connect wiring to the terminal
■
For stranded wiring
(1) Cut the wire end with cutting pliers,
then strip the insulation to expose
the stranded wiring about 10 mm and
tightly twist the wire ends. (Fig. 5-3)
(2) Using a Phillips head screwdriver,
remove the terminal screw(s) on the
terminal plate.
(3) Using a ring connector fastener or
pliers, securely clamp each stripped
wire end with a ring pressure terminal.
(4) Place the ring pressure terminal,
and replace and tighten the removed
terminal screw using a screwdriver.
(Fig. 5-4)
Insulation tape
8mm
Insulation tape
Shield mesh
Shield mesh
Fig. 5-5
Fig. 5-6
Fig. 5-7
Fig. 5-8
■
Examples of shield wires
(1) Remove cable coat not to scratch braided shield. (Fig. 5-5)
(2) Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulation tape around them. (Fig. 5-6)
(3) Remove coat of signal wire. (Fig. 5-7)
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2). (Fig. 5-8)
Screw and
Special washer
Ring
pressure
terminal
Terminal plate
Ring pressure
terminal
Screw
Special
washer
Wire
Wire
Ring
pressure
terminal
Strip 10 mm
Stranded wire
Fig. 5-3
Fig. 5-4
Big̲PAC̲eng.indb 14
2011/02/23 13:37:51
B
ig
̲P
A
C
̲e
n
g
̲m
en
tu
k
e.i
n
d
d
7
Big̲PAC̲eng̲mentuke.indd 7
2
0
1
1
/0
2
/2
3
1
3
:4
3
:3
7
2011/02/23 13:43:37
Содержание U-200PE1E8
Страница 2: ......
Страница 24: ... NOTE EN FR DE IT PT GR ES 22 ...
Страница 46: ... NOTE 44 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 68: ... ANMERKUNGEN 66 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 90: ... PROMEMORIA 88 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 112: ...EN FR DE IT PT GR ES 110 NOTAS ...
Страница 134: ... Σημεıωματάριο 132 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 156: ...EN FR DE IT PT GR ES 154 NOTAS ...
Страница 157: ......