EN
FR
DE
IT
PT
GR
ES
13
Big̲PAC̲eng.indb 23
2011/02/23 13:37:53
Big̲PAC̲eng.indb 24
2011/02/23 13:37:53
25
(Wiring procedure)
(1) Connect the remote controller to the indoor unit remote
controller wiring terminal plate (1, 2). (Remote controller
wiring)
(2) Connect the indoor units (U1, U2) and the outdoor units (1,
2). Connect the other outdoor units and indoor units (with
different refrigerant systems) in the same way. (Inter-unit
control wiring)
Connect the remote controller crossover wiring to the
indoor units (U1, U2) for each refrigerant system. (Inter-
unit control wiring)
(3) Connect the remote controller crossover wiring (2 wires)
from the remote controller wiring terminal plate (1, 2)
on the indoor unit (unit where the remote controller is
connected) to the remote controller terminal plates (1, 2)
on the other indoor units. (Remote controller crossover
wiring)
(4) Turn ON both the indoor and outdoor unit power and
perform automatic address setting from the remote
controller. (For the automatic address setting procedure,
refer to 9-8-4.)
N OT E
* Models with auxiliary heaters cannot be used for crossover
wiring of the indoor unit power wires. (Use a pull box to divide
the wiring.)
Be sure to use the indoor unit temperature sensor (body
sensor) when using this control. (Status at shipment.)
9-8-2. Setting the outdoor unit system addresses
For basic wiring diagram (Set the system address: 1)
ON
1
2
8 – 10 HP
LED1
FUSE (0.5A, F500)
OC (CN500, BLU)
MOV2
(CN301, BLK)
MOV1
(CN300, WHT)
EMG (CN502, BRN)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
R.C.ADD. Rotary switch
C2 (CN020, WHT)
C1 (CN021, WHT)
TEST (CN033, RED)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
63PH (CN027, WHT)
EXCT
(CN030, RED)
RC P
(CN039, RED)
IC002
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
FUSE
(6.3A, F101)
N . P . C H E C K
(CN046, RED)
LED2
MODE (CN038)
D115
(POWER LED)
IC001
R.C.ADD. DIP switch
A.ADD (CN047)
C-CHK (CN035)
EEPROM
LED (D041 EEPROM LED)
Fig. 9-6
System address
No.
System address
10s digit
(2P DIP switch)
System address
1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = “0”)
Both OFF
ON
1
2
“0” setting
1 (If outdoor unit is No. 1)
Both OFF
ON
1
2
“1” setting
9-8-3. Automatic address setting using the remote
controller
When the outdoor unit shown in “9-8-1. Basic wiring diagram”
is used for group control of multiple units, use the remote
controller to perform automatic address setting. (During
automatic address setting, “SETTING” blinks on the remote
controller display.)
●
Press the remote controller timer time
button and
button simultaneously. (Hold for 4 seconds or longer.) Then
press the
button. (Item code “AA” appears: All systems
automatic address setting.)
(Automatic address setting is performed in sequence for all
outdoor units from No. 1 to No. 30. When automatic address
setting is completed, the units return to normal stopped
status.)
●
To select each refrigerant system individually and perform
automatic address setting, press the remote controller timer
time
button and
button simultaneously. (Hold for
4 seconds or longer.) Then press either of the temperature
setting
/
buttons.
(Item code “A1” appears: Individual system automatic
address setting)
Use either the
or
button to select the
outdoor unit to perform automatic address setting for.
(R.C.1 is displayed.) Then press the
button. (Automatic
address setting is performed for refrigerant system 1.) When
automatic address setting for system 1 is completed, the
system returns to normal stopped status.
Again press the remote controller timer time
button and
the
button simultaneously.
Then in the same way as above (use the
button
to display “R.C.2”), select the next system and perform
automatic address setting.
9-8-4. Indicating (marking) the indoor and outdoor unit
combination number
Indicate (mark) the number after automatic address setting is
completed.
(1) So that the combination of each indoor unit can be easily
checked when multiple units are installed, ensure that the
indoor and outdoor unit numbers correspond to the system
address number on the outdoor unit control PCB, and use
a magic marker or similar means which cannot be easily
erased to indicate the numbers in an easily visible location
on the indoor units (near the indoor unit nameplates).
Example:
(Outdoor) 1 - (Indoor) 1
(Outdoor) 2 - (Indoor) 1
ON
OFF
ON
OFF
Outdoor unit control PCB
DIP switch
System address
System address rotary switch
(Set to “0” at time of shipment)
System address rotary switch
10s
20s
ON
OFF
8 – 10 HP
Big̲PAC̲eng.indb 25
2011/02/23 13:37:53
26
(2) These numbers will be needed for maintenance. Be sure to
indicate them.
* Use the remote controller to check the addresses of the
indoor units. Press and hold the
button and
button for 4 seconds or longer (simple settings mode).
Then press the
button and select the indoor
address. (Each time the button is pressed, the address
changes as follows: 1-1, 1-2, ... 2-1, 2-2, ....) The indoor
unit fan operates only at the selected indoor unit. Confi rm
that correct fan is operating, and indicate the address on
the indoor unit.
Press
the button again to return to the normal remote
controller mode.
For details, refer to the separate manual.
9-8-5. Main-sub remote controller control
Control using 2 remote controller switches
Main-sub remote controller control refers to the use of 2 remote
controllers to control 1 or multiple indoor units. (A maximum of 2
remote controllers can be connected.)
●
Connecting 2 remote controllers to control 1 indoor unit
1 2
1 2
1 2
U1U2
1 2
●
Remote controller setting mode
To set the remote controller main/sub setting or change the
sensor, follow the steps below.
(1) Press both and buttons on the remote controller
for more than 4 seconds together.
(2) Select CODE No. with / ( ) buttons.
(3) Change DATA with / (TIMER) buttons.
(4) Press . Finally, press
.
DATA is memorized in the RCU. (DATA setting will not be
changed even when the power is turned off.)
Make sure to set [Normal] for RCU. CK.
RCU. Main/Sub
Main
Sub
CODE
ITEM
DATA
ITEM
Clock display
12 hours
(AM/PM)
24 hours
RCU. CK
Normal
RCU. CK
Room temperature sensor Main unit
RCU
9-9. Test Run Procedure
NO
YES
NO
YES
NO
YES
Fig. 9-7
Recheck the items to check
before the test run.
(See 9-10)
Check the combination (wiring) of
indoor and outdoor units.
(See 9-15)
Is system “single-type”?
(1 indoor unit is connected
to 1 outdoor unit)
Are multiple outdoor units
used?
Turn ON the indoor and
outdoor power.
Set the indoor unit control
switch to “TEST”.
(Automatic Address Setting)
(See 9-12)
Can operation be
started?
Slide the indoor unit control
switch back to “ON”.
(See 9-12)
Turn ON the
indoor and
outdoor power
(Automatic
Address setting)
(See 9-15-2) In
case of group
control
Confirm wiring
is done in
accordance with
Fig. 2, “Basic
Wiring”.
(See 9-15-3 to
9-15-6)
How to Set
Automatic Address
Set the
automatic
address setting
from outside unit.
(See 9-14)
Refer to “Table of Self-
Diagnostic Functions”
to check the system.
In addition, refer to
9-15 and correct any
items that need to be
corrected.
Note: Check the indoor-
side drainage.
Remote controller wiring
Terminal plate for remote
controller wiring
Remote controller
switch (main)
Optional
Optional
Remote controller
switch (sub)
Ground
Ground
Indoor unit
Outdoor unit
Big̲PAC̲eng.indb 26
2011/02/23 13:37:54
B
ig
̲P
A
C
̲e
n
g
̲m
en
tu
k
e.i
n
d
d
1
3
Big̲PAC̲eng̲mentuke.indd 13
2
0
1
1
/0
2
/2
3
1
3
:4
3
:4
1
2011/02/23 13:43:41
Содержание U-200PE1E8
Страница 2: ......
Страница 24: ... NOTE EN FR DE IT PT GR ES 22 ...
Страница 46: ... NOTE 44 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 68: ... ANMERKUNGEN 66 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 90: ... PROMEMORIA 88 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 112: ...EN FR DE IT PT GR ES 110 NOTAS ...
Страница 134: ... Σημεıωματάριο 132 GB FR DE IT PT GR ES SUPPLEMENT ...
Страница 156: ...EN FR DE IT PT GR ES 154 NOTAS ...
Страница 157: ......