Functions
3-5 Releasing Lockout
Lockout is always released after source of error has been removed.
Lockout is released by manually operating the switch connected to between INT11 and INT12.
● Overall reset (manual start) : The reset switch functions as a lockout release switch.
Switching the switch from “Close” to “Open” can release lockout.
INT11
INT21
INT12
INT22
With external device monitor
INT11
INT21
INT12
INT22
Without external device monitor
● Overall reset (auto start) : Momentary type switch is connected to between INT11 and
INT12.
When this device is put in lockout status, the switch functions as
a lockout release switch.
Switching the switch from “Close” to “Open” can release lockout.
<Reference>
When INT11-INT12 and INT21-INT22 are simultaneously “Closed” during overall reset (auto
start), “Reset input circuit error” turns this device into lockout status. In this case, “
” appears in
7-segment indicator (red).
In this case, release lockout by operating the switch again to switch “Close” to “Open.”
With external device monitor
INT11
INT21
INT12
INT22
Without external device monitor
INT11
INT21
INT12
INT22
● Partial reset (auto start)
: Alternate type switch is connected to between INT11 and INT12.
Switching “from Open to Close to Open” can release lockout.
After the release of lockout, set the switch to “Close.”
With external device monitor
INT11
INT21
INT12
INT22
Without external device monitor
INT11
INT21
INT12
INT22
After the release of lockout, the operation is performed as follows:
● Manual reset : Manual reset turns the control output into ON status.
● Auto reset : Auto reset turns the control output into ON status.
CAUTION
When the safety input condition of this device is satisfied, release of lockout turns the control out
-
put into ON status in the case of auto reset setting. To prevent unexpected startup of the machine,
secure safety for the overall system.