Configuration Check
5-20 Configuration Check
A logic created in the main screen is checked. If an error exists on a dangerous side, the target
input block, control block and connection tab are highlighted in red frames.
Only the faults that lead to danger are determined as errors.
Combinations of input blocks and control block 1
: Mandatory
: Connectable
: Not connectable
Control block 1
AND
OR
P-MUTE
S-MUTE
Two-hand
control
Select
input
Number of input connections
2 to 4
2 to 4
2 or 3
3 or 4
2
3
Input block
2NC
×
×
1NO/1NC
×
×
PNP×2 (equ.)
Note 1
Note 1
PNP×2 (dif.)
Note 1
Note 1
Muting input (equ.)
Note 2
Note 3
Muting input (dif.)
Note 2
Note 3
Override
Key selector
PNP×1
1NC
Test
No logic
Notes: 1) For either PNP×2 (equ.) or PNP×2 (dif.), only one connection is allowed.
2) For either Muting input (equ.) or Muting input (dif.), only one connection is allowed.
3) For either Muting input (equ.) or Muting input (dif.), two connections are allowed.
Combinations of input blocks and control block 2 / 3, and connection tab E / F
: Connectable
: Not connectable
Control block 2
Control block 3
AND
OR
AND
OR
Number of input connections
2 to 4
2 to 4
2 to 4
2 to 4
Input block
2NC
1NO/1NC
PNP×2 (equ.)
PNP×2 (dif.)
Muting input (equ.)
Muting input (dif.)
Override
Key selector
PNP×1
1NC
Test
No logic
Connection tab E
Connection tab F