Chapter 1. Programming Site Data
42
DigitalFlow™ DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual (2-Channel)
1.7.6
Setting Up Serial Communications
The Model DF868 flowmeter can transmit stored data and displayed readings to a remote ANSI terminal or a
personal computer by connecting the meter’s RS232 interface to the serial port of the PC. In addition, the Model
DF868 can receive and execute remote commands via this link.The meter can also be configured with a MODBUS
option card for MODBUS (RS485) communications, a Foundation Fieldbus option card for Foundation Fieldbus
communications, or a MODBUS/TCP option card for MODBUS communications over the Ethernet, if desired.
Note:
To set Fieldbus communications parameters, see Appendix D,
Foundation Fieldbus Communications
.
Use the
COMM
submenu to set the RS232, MODBUS, Ethernet and MODBUS/TCP communications port parameters
and to enter a network identification number. A network identification number is required to use the Panametrics
Instrument Data Manager
or
PanaView
software. While following the programming instructions, refer to the menu
1.
To enter the
GLOBAL
menu, press
[F3]=GLOBL.
2.
To enter the
COMM
submenu, press [
and
[F4]
.
3.
Use the
[F1]-[F4]
and [
keys to select the desired
Baud Rate
.
Note:
As shown in Figure 14 on page 101, the available rates are 300, 600, 1200, 2400, 4800, 9600 and 19,200 baud.
4.
Use the
[F1]-[F4]
and [
keys to select the desired
UART Bits
. The five available responses are listed in Table 25.
5.
Enter a
Network ID
number between 1 and 254 and press
[ENT]
. The default number is 1
A network ID number is only necessary for communication with the Panametrics
Instrument Data Manager
(IDM) or
PanaView
software. See the software
User’s Manual
(910-185) for more information.
IMPORTANT:
If the network ID number is changed, communication with the Instrument Data Manager or PanaView
must be re-established with the new ID number.
Table 25: UART Bits Options
Option Bar
# Data Bits
# Stop Bits
Parity
8,no
8
0
None
8,odd
8
0
Odd
8even
8
0
Even
7,odd
7
1
Odd
7even
7
1
Even
Содержание DigitalFlow DF868
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 10: ...Contents viii DigitalFlow DF868 Programming Manual 2 Channel...
Страница 104: ...Appendix A Menu Maps 96 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 118: ...Appendix B Data Records 110 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 150: ...Appendix E OPC Server 142 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 158: ...2 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 159: ......