Chapter 1. Programming Site Data
36
DigitalFlow™ DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual (2-Channel)
Slot X Analog Outputs (cont.)
4.
Use the [
and [
and
[F1]-[F4]
keys to specify the desired
Output Measurement
parameter, as shown in
Table 21.
The
DIAG
option provides access to a wide variety of diagnostics parameters. See Chapter 3,
Diagnostics
, of the
Service Manual
for a complete description of these options.
Note:
The measurement units that appear in these prompts are those selected in the
GLOBL-SYSTM
menu earlier
in this chapter.
5.
Enter a value for the
Base
(low end) of the chosen output range and press
[ENT]
.
6.
Enter a value for the
Full
(high) end of the chosen output range and press
[ENT]
.
7.
Use the
[F1]-[F4]
keys to select the desired
Error Option
, the way the display responds during an error condition.
Available options are shown in Table 22.
8.
Press
[F1]
-
[F4]
to set up another output or press
[EXIT]
to select another slot for set up.
For instructions on setting up additional inputs and/or outputs proceed to the appropriate section. Otherwise, press
[EXIT]
twice to return to the
Global Program
prompt.
Table 21: Output Measurement Options
Option Bar Choice
Description
[F1]
=
VEL
Flow Velocity
[F2]
=
VOLUM
Volumetric Flow
[F3]
=
+TOTL
Forward Totalized Volume Flow
[F4]
=
-TOTL
Reverse Totalized Volume Flow
[
+ [F1]
=
MDOT*
Mass Flow
[
+ [F2]
=
+MASS*
Forward Totalized Mass Flow
[
+ [F3]
=
-MASS*
Reverse Totalized Mass Flow
[
+ [F4]
= POWER**
Energy Flow Power
[
+ [
+ [F1]
= +ENRG**
Forward Energy Flow
[
+ [
+ [F2]
= -ENRG**
Reverse Energy Flow
[
+ [
+ [F3]
=
DIAG
Diagnostic
* Available only if
Mass Flow (static)?
=
YES
**Available only if Energy Option = YES
Table 22: Error Response Options
Option
Display Response
HOLD
Holds the last “good” reading.
LOW
Forces the outputs to the low setpoint.
HIGH
Forces the outputs to the high setpoint.
OTHER
Allows user to enter 4-20 mA error level in mA.
Содержание DigitalFlow DF868
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 10: ...Contents viii DigitalFlow DF868 Programming Manual 2 Channel...
Страница 104: ...Appendix A Menu Maps 96 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 118: ...Appendix B Data Records 110 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 150: ...Appendix E OPC Server 142 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 158: ...2 DigitalFlow DF868 Multipurpose Ultrasonic Liquid Flowmeter Programming Manual 2 Channel...
Страница 159: ......