AFX SERIES® OPERATION MANUAL
SECTION 5: UNPACKING AND INSTALLATION
Entire Contents Copyright
2016 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 59 of 274
5.14.11
Cabinet Load Connections – Single Phase Loads
Note that the Neutral connection for single phase loads will have to carry all the line current
so the wire size must be chosen accordingly. Since AFX cabinets come standard with a three
phase output terminal block, the three output terminals A,B and C must be shorted
together, either at the load or at the output terminal block as shown in the diagram below.
L
N
Figure 5-16: Single Phase Load Connection Diagram
Содержание 3120AFX