AFX SERIES® OPERATION MANUAL
SECTION 8: REMOTE PROGRAMMING
Entire Contents Copyright
2016 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 154 of 274
8.6.1.1
Steady State Output Parameter List Table
The following table details the available parameters for the steady state program
definitions.
Parameter
Description
FORM,<n>
sets Output Power Form of selected program
n = <1>Single Ф, <2>Split Ф, or <3>Three Ф
COUPLing,<s>
sets Output coupling of selected program
s = <DIRECT> or <XFMR>
XFMRRATIO,<n.nn>
sets Output XFMR ratio (n.nn:1) of selected program
n.nn = <0.01> to <5.11>
FREQuency,<n>
sets Output Frequency of selected program
n = <:SOUR:FREQ:LIM:MIN> to <:SOUR:FREQ:LIM:MAX> Hz
VOLTage,<n>
sets Output VOLTAGE ФA,B,C of selected program
n = <0> to <300 x XFMRRATIO> Volts
VOLTage1,<n>
sets Output VOLTAGE ФA of selected program
n = <0> to <300 x XFMRRATIO> Volts
VOLTage2,<n>
sets Output VOLTAGE ФB of selected program
n = <0> to <300 x XFMRRATIO> Volts
VOLTage3,<n>
sets Output VOLTAGE ФC of selected program
n = <0> to <300 x XFMRRATIO> Volts
CURRent:LIMit,<n>
sets Output Current Limit of selected program
n = <0> to <AMPS meter range> Amps
CURRent:PROTect:LEVel,<n>
sets Output Current level that triggers Current Protect mode
n = <0> to <AMPS meter range> Amps
CURRent:PROTect:TOUT,<n>
sets time that the Output Current must exceed the Current Protect
level before Current Protect disables the power source output.
n = <1> to <65535>, 1 = 100mSec.
PHASe2,<n>
sets Output Phase Angle B of selected program
n = <0> to <359> degrees
PHASe3,<n>
sets Output Phase Angle C of selected program
n = <0> to <359> degrees
WAVEFORM,<n>
sets Output Waveform ФA, ФB, ФC of selected program
n = <1> to <16>
WAVEFORM1,<n>
sets Output Waveform ФA of selected program
n = <1> to <16>
WAVEFORM2,<n>
sets Output Waveform ФB of selected program
n = <1> to <16>
WAVEFORM3,<n>
sets Output Waveform ФC of selected program
n = <1> to <16>
EVENTS,<n>
sets number of times to repeat the transient portion of the selected
program when the Transient is executed
n = 0-65535. A value of 0 specifies continuous operation
AUTORMS,<n>
program Transient Waveform Auto RMS mode (4.5.2) n = 0, use
program steady-state waveform RMS factor n = 1, calculate RMS
factor based on transient waveform
Содержание 3120AFX
Страница 273: ......