AFX SERIES® OPERATION MANUAL
SECTION 8: REMOTE PROGRAMMING
Entire Contents Copyright
2016 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 184 of 274
Command Syntax
[SOURce:]CURRent:LIMit:AUTO
Description
This commands enables or disables the Auto Current Limit function.
This function automatically adjusts the programmed current limit level
as a function of programmed voltage along the constant power curve
of the voltage range.
For example: On a 3150AFX model in three phase mode, if VOLT = 0
and CURR:LIM = 40 and voltage is changed to V = 300, the CURR:LIM
will change to: 5000 VA / 300 Vac = 16.0.
If CURR:LIM:AUTO = OFF then the CURR:LIM setting will remain at 40A
and the power source will power limit at 5000VA instead if the load
draws more than 16Aac.
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b>
Example
CURR:LIM:AUTO ON
Query Format
[SOURce:]CURRent:LIMit:AUTO?
Returned Data Format
<b>
Query Example
CURR:LIM?
1
Command Syntax
[SOURce:]CURRent:PROTect:TOUT
Description
This command sets the programmable delay to hold off when the
current trip protection level is exceeded. If the load current remains at
or above this current level during this time period, the output will turn
off at the end of the time delay.
Note: This command serves the same purpose as the
“[SOURce:]PROTect”TDELAY” command and is provided for backward
compatibility with PPS UPC controllers.
Parameters
0 – 65535
Parameter Format
<nr1>
Example
CURR:PROT:TOUT 2
Query Format
[SOURce:]CURRent:PROTect:TOUT?
Returned Data Format
<nr1>
Query Example
CURR:PROT:TOUT?
2
Содержание 3120AFX
Страница 273: ......