Regular Inspections
Section 7-2
7-2
Regular Inspections
To maintain the V530-R150 in the best condition, perform the follow-
ing regularly.
• Lightly wipe off dirt with a soft cloth.
• Clean the lens and indicators with a cloth for a lens or air brush.
Note
1.
Turn OFF the power and take safety precautions before conduct-
ing inspections.
2.
Do not use thinners or benzene.
Inspection Items
Details
Required Tools
Power Supply
The voltage measured at the power supply terminals on
the terminal block must be 24 VDC (+10%, –15%).
Circuit Tester
Ambient Temper-
ature
The operating ambient temperature inside the cabinet
must be between 0 to +50
C.
Thermometer
Ambient Humidity
The operating ambient humidity inside the cabinet must
be between 35 and 85%.
Hygrometer
Installation
Each cable connector must be correctly inserted and
locked.
The cameras must be firmly secured.
The camera lens mounts must be firmly secured.
Phillips screw
driver
Содержание V530-R150E-3 -
Страница 1: ...Cat No Z155 E1 01 2 Dimensional Code Reader Fixed Type V530 R150E 3 V530 R150EP 3 OPERATION MANUAL...
Страница 2: ...V530 R150E 3 V530 R150EP 3 2 Dimensional Code Reader Fixed Type Operation Manual Produced August 2001...
Страница 7: ......
Страница 9: ......
Страница 17: ......
Страница 27: ......
Страница 47: ......
Страница 63: ......
Страница 224: ...207 System Section 6 4 2 Set each item 3 Select End before leaving this screen...
Страница 226: ...209 System Section 6 4 2 Select the error method 3 Select End to leave this screen...
Страница 247: ...230 2 Dimensional Code Reader Section 8 1 8 1 2 Dimensional Code Reader V530 R150 Four 4 5 dia 165 min Unit mm...
Страница 263: ......
Страница 279: ......
Страница 281: ......
Страница 283: ......
Страница 289: ......