686
Auxiliary Area Allocations by Address
Appendix D
A401
A401.14 I/O Bus Error
Flag
(fatal error)
ON in the following cases:
• When an error occurs in a data
transfer between the CPU Unit
and a CP-series Expansion Unit or
Expansion I/O Unit. If this hap-
pens, 0A0A hex will be output to
A404.
• When an error occurs in a data
transfer between the CPU Unit
and a CJ-series Unit. If this hap-
pens, 0000 hex will be output to
A404 to indicate the first Unit,
0001 hex to indicate the second
Unit, and 0F0F hex to indicate an
undetermined Unit.
• When the End Cover is not
attached to the last CJ-series Unit.
If this happens, 0E0E hex will be
output to A404.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
(This flag will be turned OFF when
the error is cleared.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A404
A401.15 Memory Error
Flag
(fatal error)
ON when an error occurred in mem-
ory or there was an error in auto-
matic transfer from the Memory
Cassette when the power was turned
ON.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
The location where the error
occurred is indicated in A403.00 to
A403.08, and A403.09 will be turned
ON if there was an error during auto-
matic transfer at startup.
This flag will be turned OFF when
the error is cleared. (The automatic
transfer at startup error cannot be
cleared without turning OFF the
PLC.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A403.00
to
A403.08,
A403.09
A402
A402.00 Other Fatal
Error Flag
ON when a non-fatal error that is not
defined for A402.01 to A402.15
occurs. Detailed information is output
to the bits of A314.
There are no errors that affect this
flag at this time. This flag is reserved
by the system.
OFF: No
other fatal
error
ON: Other
fatal error
Cleared
Cleared
Refreshed
when error
occurs.
A315
A402.04 Battery Error
Flag
(non-fatal
error)
ON if the CPU Unit’s battery is dis-
connected or its voltage is low and
the Detect Battery Error setting has
been set in the PLC Setup.
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
This flag can be used to control an
external warning light or other indica-
tor to indicate that the battery needs
to be replaced.
(This flag will be turned OFF when
the error is cleared.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
PLC
Setup
(Detect
Battery
Error)
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......