120
Wiring CP1H CPU Units
Section 3-4
• The GR terminal is a ground terminal. To prevent electrical shock, use a
dedicated ground line (2 mm
2
min.) of 100
Ω
or less.
• The line ground terminal (LG) is a noise-filtered neutral terminal. If noise
is a significant source of errors or if electrical shocks are a problem, con-
nect the line ground terminal (LG) to the ground terminal (GR) and ground
both with a ground resistance of 100
Ω
or less.
• To prevent electrical shock when short-circuiting between the LG and GR
terminals, always use a ground of 100
Ω
or less.
• Do not connect ground lines to other devices or to the frame of a building.
Doing so will reverse the effectiveness of the ground and instead have a
bad influence.
Isolating Transformer
The PLC's internal noise control is sufficient for the general noise to which
power supply lines are subjected. Ground noise can be further reduced by
providing the power supply through a 1:1 isolating transformer. Leave the iso-
lating transformer's secondary side ungrounded.
CPU Units with DC Power Supply
DC Power Supply Wiring
• Use crimp terminals or solid wire for wiring the power supply. Do not con-
nect bare stranded wires directly to terminals.
• M3 self-rising terminal screws are used. Tighten the terminal screws to
the torque of 0.5 N·m.
• To prevent noise, use a ground of 100
Ω
or less.
DC Power Supply
• Provide a power supply of 20.4 to 26.4 VDC unless there are two or more
Expansion Units and Expansion I/O Units. Provide a power supply of 21.6
to 26.4 VDC if there are two or more Expansion Units and Expansion I/O
Units.
• The maximum current consumption is 50 W per device.
• When the power supply is turned ON, the inrush current is approximately
five times the normal current.
• The GR terminal is a ground terminal. To prevent electrical shock, use a
dedicated ground line (2 mm
2
min.) of 100
Ω
or less.
Note
(1) Never reverse the positive and negative leads when wiring the power sup-
ply terminals.
(2) Supply all power to the power supply terminals from the same source.
+
−
COM
01
03
05
07
09
11
01
03
05 07
09 11
NC
00 02
04
06
08
10
00
02
04
06
08
10
−
+
24 VDC
Circuit protector
Upper terminal block
Ground (100
Ω
or less)
GR: Protective ground terminal
6.2 mm max.
6.2 mm max.
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......