337
Analog I/O (XA CPU Units)
Section 5-5
Writing Analog Output SV
Data
The ladder program can be used to write data to the memory area words
where the set value is stored. Write the output SV data to CIO 210 to CIO
211.
The Analog Initialization Completed Flag (A434.04) indicates when the built-in
analog I/O has been initialized.
Startup Operation
After power is turned ON, it takes approximately 1.5 s before the initial data is
converted and stored in the input words. The Analog Initialization Completed
Flag (A434.04) will go ON when initial processing is completed. If the system
starts operating, use this flag in the program to delay reading converted data
from analog inputs until the data is valid.
Handling Unit Errors
When an error occurs in the built-in analog I/O system, analog input data will
be set to 0000 and the analog output will be set to 0 V or 0 mA.
If a CPU error occurs, the analog output will be set to is set to 0 V or 0 mA
even if the output range is 1 to 5 V or 4 to 20 mA. For any other fatal errors in
the CPU Unit, 1 V or 4 mA will be output if the output range is 1 to 5 V or 4 to
20 mA.
!Caution
If an interrupt task program is executed continuously for more than 6 ms, the
built-in analog function will not operate properly and a Built-in Analog Error
will occur. When using the built-in analog function, design the system so that
interrupt task programs are not executed too long or too frequently. Test the
system thoroughly in trial operation before operating the system.
Bit
Function
A434.04
Analog Initialization Completed Flag
0: Initializing
1: Initialization completed
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......