471
Temperature Sensor Units
Section 7-5
Input Word
Output Word
Read/Response Command and Temperature Data
• Negative values are stored as 2’s complements.
• The converted temperature data CIO m+2 is stored in 16-bit binary data
(4-digit hexadecimal).
• Data for range codes that include one digit after the decimal point are
stored without the decimal point, i.e., 10 times the actual value is stored.
• If the input temperature exceeds the maximum or minimum value in the
temperature input range that has been set by ±20
°
C or ±20
°
F, the dis-
played value will be held.
• If the circuit is disconnected, the open-circuit detection function will oper-
rate and the converted temperature data will be set to 7FFF.
• The open-circuit detection function will be automatically cleared and nor-
mal input temperature conversion will begin automatically when the input
temperature returns to the convertible range.
m+1
Response. Input words stored in CIO m+2
m+2
Temperature data of the specified input word
n+1
Read command data (input word specified)
Command
Output
Word
Input Word
n+1
m+1
m+2
Read
command
Response
command
Temperature data
(4-digit hexadecimal)
Read temperature data from input 0 #9901
9901
Input 0 temperature data
Read temperature data from input 1 #9902
9902
Input 1 temperature data
Read temperature data from input 2 #9903
9903
Input 2 temperature data
Read temperature data from input 3 #9904
9904
Input 3 temperature data
Read temperature data from input 4 #9905
9905
Input 4 temperature data
Read temperature data from input 5 #9906
9906
Input 5 temperature data
Read temperature data from input 6 #9907
9907
Input 6 temperature data
Read temperature data from input 7 #9908
9908
Input 7 temperature data
Read temperature data from input 8 #9909
9909
Input 8 temperature data
Read temperature data from input 9 #990A
990A
Input 9 temperature data
Read temperature data from input 10 #990B
990B
Input 10 temperature data
Read temperature data from input 11 #990C
990C
Input 11 temperature data
Others
Others
No response for other commands
Input
Data conversion examples
Unit: 0.1
°
C
K or J
×
10
500.0
°
C
→
5000
→
1388 hex
−
20.0
°
C
→
−
200
→
FF38 hex
−
200.0
°
C
→
−
2000
→
F830 hex
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......