333
Analog I/O (XA CPU Units)
Section 5-5
1. Setting the Analog Voltage/Current Input Switches
Each analog input can be set for use as a voltage input or current input.
Each input’s input range is set independently in the PLC Setup. The voltage
input range can be set to 0 to 5 V, 1 to 5 V, 0 to 10 V, or
−
10 to 10 V. The cur-
rent input range can be set to 0 to 20 mA or 4 to 20 mA.
Note
The built-in analog input switch is located on the PCB inside the case. To
make setting the switch easier, make the switch settings before mounting the
terminal block to the base.
When setting this switch, be very careful not to damage the wiring on the
PCB.
2. PLC Setup
Use the CX-Programmer to set the various PLC Setup including whether the I/
O point is being used, the input range, output range, averaging function
usage, and resolution. The I/O point usage, input range, output range, and
averaging function usage can be set independently for each I/O point, but the
resolution setting applies to all of the I/O points.
• The input range can be set to
−
10 to 10 V, 0 to 10 V, 1 to 5 V, 0 to 5 V, 0 to
20 mA or 4 to 20 mA.
• The output range can be set to
−
10 to 10 V, 0 to 10 V, 1 to 5 V, 0 to 5 V, 0
to 20 mA or 4 to 20 mA.
• Once the range has been set, it cannot be changed as long as the CP1H
CPU Unit’s power is ON. To change the input range or output range,
change the setting in the PLC Setup, turn the CPU Unit OFF, and then
turn the CPU Unit ON again.
ON
1
2
3
4
ON
OFF
Analog input 4 selection switch
Analog input 3 selection switch
Analog input 2 selection switch
Analog input 1 selection switch
OFF: Voltage input (factory default setting)
ON: Current input
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......