585
Trouble Shooting
Section 9-11
9-11-2 Trouble-shooting with Indicators and Error Code Display
9-11-3 Error Status
The status of errors that occur at the Ethernet Option Board is reflected in CIO
relation area, Refer to
9-9-1 CIO Area Allocation, Error Status
for details.
ERR
Indicator
Error
Probably Cause
Error code
(hex)
Correction
Lit
CPU Unit service
monitoring error
Service from the CPU
Unit was not completed
within the fixed interval.
The monitoring time is
normally 11s.
0002
Check and correct the CPU Unit’s operating
environment.
Check whether the related DIP SW is on.
9-8-2 Installation and Removing
Note
Recovery is possible for this error.
When operation is restored, it will
return to normal.
Two option boards
(unit version 1.0)
installed
Two option boards
have been installed on
the CPU Unit.
---
Uninstall the Ethernet Option Board in one
serial port of the CPU Unit and restart the
CPU unit.
Option board error
An error occurred in
the Ethernet Option
Board.
0601
Restart the CPU Unit. Replace the Ethernet
Option Board if the error recurs.
Option board
memory error
An error occurred in
the Unit’s non-volatile
memory itself. This
error will occur while
writing or reading the
error log, system setup,
identity data, MAC ID.
0602
Restart the CPU Unit. Replace the Ethernet
Option Board if the error recurs.
Flashing
CPU Unit fatal
error
A fatal error occurred in
the CPU Unit.
0015
Eliminate the cause of the error in the CPU
Unit.
IP address setting
error
The IP address is set
incorrectly.
021A
Correct the IP address. Do not set any of
the following IP addresses.
•
Host IDs that are all 0 or all 1.
•
Network IDs that are all 0 or all 1.
•
Subnetwork IDs that are all 1.
•
Addresses beginning with 127 (7F hex).
IP address table
error
The IP address table is
set incorrectly.
021A
Correct the IP address table.
IP Router table
setting error
The IP Router table is
set incorrectly.
021A
Correct the IP Router table.
Address
Disagreement
The node number set
for the option board
does not agree with the
host ID in the IP
address. This probably
occurs when the
address conversion
method is set for auto-
matic address genera-
tion.
021A
Make sure that the node number and the last
byte of the IP address are the same and then
set other host IDs to 0.
Change the address conversion method.
Logic error in
setting table
There is a logic error in
the setting table.
021A
Recreate the data specified by the 2nd byte
of the detailed error code.
System setup Sum
check error
The Checksum of Sys-
tem setup is incorrect.
03D0
Reset the value of system setup area.
Restart the CPU Unit.
FINS/TCP setting
error
The settings of
FINS/TCP are
incorrect.
03C0
Refer to operation manual and set the
FINS/TCP setting correctly.
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......