164
DeviceNet Area
Section 4-8
The following words are allocated to the DeviceNet Unit when the remote I/O
slave function is used with fixed allocations.
The DeviceNet Area can be used in programming if a CJ-series DeviceNet
Unit is not used.
Forcing Bit Status
Bits in the DeviceNet Area can be force-set and force-reset.
Note
There are two ways to allocated I/O in DeviceNet networks: Fixed allocations
according to node addresses and user-set allocations.
• With fixed allocations, words are automatically allocated to the slaves in
the specified fixed allocation area according to node addresses.
• With user-set allocations, the user can allocate words to Slaves from the
following words.
CIO 17 to CIO 99, CIO 117 to CIO 6143(See note.)
W0 to W511
H0 to H511
D0 to D32767
For details on word allocations, refer to the
DeviceNet Operation Manual
(W267)
.
Note
0~16CH cannot be assigned as input relay area and 100~116CH as
output relay area.
For XA type, 200~203CH and 210~213CH cannot be assigned as
built-in analog input/output area.
DeviceNet Area
Initialization
The contents of the DeviceNet Area will be cleared in the following cases:
1.
When the operating mode is changed from PROGRAM to RUN or MONI-
TOR mode or vice-versa and the IOM Hold Bit is OFF
2.
When the power is cycled
3.
When the DeviceNet Area is cleared from the CX-Programmer
4.
When PLC operation is stopped when a fatal error other than an
FALS(007) error occurs (The contents of the DeviceNet Area will be re-
tained when FALS(007) is executed.)
Area
Output Area
(master to slaves)
Input Area
(slaves to master)
Fixed Allocation Area 1
CIO 3370
CIO 3270
Fixed Allocation Area 2
CIO 3570
CIO 3470
Fixed Allocation Area 3
CIO 3770
CIO 3670
CPU Unit
DeviceNet
Master Unit
DeviceNet Area
DeviceNet
Slaves
With fixed allocation, words are assigned according to node
numbers. (If a Slave requires two or more words, it will be
allocated as many node numbers as words required.)
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......