List of Constants Used with 3G3EV
Standard Model
Constant
no.
Indi-
cators
Description
Setting range
Setting
n01
Constant
0: Only n01 can be set.
write-inhibit
1: All constants can be set.
selection
8: Constant settings are initialized.
/constant
initialization
9: Inverter is initialized in 3-wire
sequence mode.
n02
Mode operation
selection
Run command
Frequency
reference
0
Digital Operator
Digital Operator
1
Control terminal
Digital Operator
2
Digital Operator
Control terminal
(voltage input)
3
Control terminal
Control terminal
(voltage input)
4
Digital Operator
Control terminal
(amperage
input)
5
Control terminal
Control terminal
(amperage
input)
n03
Stop mode
0: Deceleration stop
selection
1: Free running
n04
Forward
/Reverse
f%r
: forward rotation
rotation
selection
reU
: reverse rotation
n06
Multi-function
0: Forward/reverse rotation command
input selection
1: Fault reset
2: External fault (external fault when ON)
3: External fault (external fault when
OFF)
4: Multi-step speed command
n09
Multi-function
0: Fault occurrence
output selection
1: Operation in progress
2: Frequency matching
n11
Frequency
reference 1
0.0 to 400 (Hz)
[6.0]
n12
Frequency
reference 2
0.0 to 400 (Hz)
[0.0]
n20
Acceleration
time
0.0 to 999 (seconds)
[10.0]
Appendix A
Chapter 7
Содержание SYSDRIVE 3G3EV SERIES
Страница 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Страница 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Страница 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 32: ...Chapter 4 Preparing for Operation 4 1 Preparation Procedure 4 2 Using the Digital Operator 4 3 Test Run 4...
Страница 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...