4-11
Note 3. The setting range for the 400-VAC models is “1 to 5.”
Note 4. The factory setting for the 3G3EV-A4015-CUE is “3.”
Note 5. Displaying the constant no. corresponding to an indicator in the “Dedicated
indicator” column lights the indicator.
Note 6. Constant no. 02 (n02) and subsequent constants can be set only when
constant no. 01 (n01) is set to 1.
Constants in the shaded areas in the above table may not be usable depending on the
PROM number (software version).
Con-
PROM no. (software version)
stant
no.
199 or lower
200
220 or higher
n03
No
Yes
Yes
n39
Setting range: 0.10 to 2.00 Setting range: 0.10 to 2.00 Setting range: 0.10 to 2.55
n61
No
Yes
Yes
n64
No
No
Yes
Note “Yes” indicates that the constant can be set.
“No” indicates that the constant cannot be set.
H
Details of Each Constant
n01
Constant Write-Inhibit Selection/Constant Initialization
Setting range
0, 1, 8, 9
Factory setting 1
One of the following four values can be selected:
Value
Description
0
Only n01 can be set.
1
Constants n01 to n68 can be displayed and set.
8
All constants are returned to factory settings.
9
The Inverter is initialized in 3-wire sequence mode.
Note 1. If other constants are to be set, always set “1” in n01.
Note 2. Setting “9” (3-wire sequence mode) in n01 allows the user to start and stop the
Inverter with automatic recovery type push-button switches.
Preparing for Operation
Chapter 4
Содержание SYSDRIVE 3G3EV SERIES
Страница 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Страница 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Страница 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 32: ...Chapter 4 Preparing for Operation 4 1 Preparation Procedure 4 2 Using the Digital Operator 4 3 Test Run 4...
Страница 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...