4-20
n36
Operation after Recovery from Power Interruption
Setting range
0, 1, 2
Factory setting 0
This constant is used to select the processing to be performed after recovery from an
instantaneous power interruption.
Value
Description
0
Discontinues operation.
1
Continues operation only if power interruption is within 0.5 second.
2
Continues operation unconditionally (with no error output).
Note If “1” or “2” is selected to continue operation, the Inverter automatically searches
the motor speed (even when the motor is in a free-running state) and continues
smooth operation. This function is called the speed search function.
Explanation of Speed Search Function
Motor speed
Free-running state
Inverter starts operating
Time
n37
Carrier Frequency
Setting range
1, 2, 3, 4
(see note 1)
Factory setting 4 (10 kHz)
(see note 2)
This constant is used to set a pulse-width-modulated (PWM) carrier frequency.
Value
Carrier frequency
1
2.5 (kHz)
2
5 (kHz)
3
7.5 (kHz)
4
10 (kHz)
5
12.5 (kHz)
Note As the cable between the Inverter and the motor becomes longer, a high-frequen-
cy leakage current from the cable increases, causing the Inverter output current
to increase as well. This may also affect peripheral devices. To prevent this, ad-
just the carrier frequency according to the following standards:
S
Cable length of 50 meters or less: 10 kHz or less
S
Cable length of 50 to 100 meters: 5 kHz or less
Note 1. The setting range for the 400-VAC class is “1 to 5.”
Preparing for Operation
Chapter 4
Содержание SYSDRIVE 3G3EV SERIES
Страница 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Страница 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Страница 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 32: ...Chapter 4 Preparing for Operation 4 1 Preparation Procedure 4 2 Using the Digital Operator 4 3 Test Run 4...
Страница 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...