4-13
Note 2. The DIP switch is located inside the Inverter. Use this switch to change the set-
ting when frequency references are to be input in terms of amperage (4 to 20
mA). For details, refer to Section 7-2 Frequency Reference by Amperage Input.
For voltage input, never set the DIP switch to ON. Doing so may damage the
equipment.
n03
Interruption Mode Selection
Setting range
0, 1
Factory setting 0
This constant is used to specify the interruption mode when the STOP/RESET Key is
pressed or the operation command is OFF.
Value
Description
0
Frequency deceleration stop
1
Free running
Example of Frequency Deceleration Stop
Output frequency
Forward rotation
(Reverse rotation)
Operation command
Deceleration time 1
Minimum output frequency determined
with constant set in n29: Factory-set to
1.5 kHz
Time
Interruption DC control time determined
with constant set in n47: Factory-set to 0.5
second
ON
OFF
(n21)
Example of Free Running
Output frequency
Inertia of motor
Time
Forward rotation
(Reverse rotation)
Operation command
ON
OFF
Note This constant is available for models with a PROM number (software version) of
“200” or higher.
Preparing for Operation
Chapter 4
Содержание SYSDRIVE 3G3EV SERIES
Страница 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Страница 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Страница 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 32: ...Chapter 4 Preparing for Operation 4 1 Preparation Procedure 4 2 Using the Digital Operator 4 3 Test Run 4...
Страница 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...