6-3
Three
Model 3G3EV-
---
A4002(-
j
) A4004(-
j
) A4007(-
j
) A4015(-
j
)
phase,
400 VAC
Power
supply
Rated voltage
and frequency
Three-phase, 380 to 460 VAC, 50/60 Hz
Allowable
voltage
fluctuation
–15% to 10 %
Allowable
frequency
fluctuation
±
5%
Heating value (W)
---
25.5
34.7
56.0
78.5
Weight (kg)
---
1.0
1.0
1.5
2.0
Maximum applicable motor capacity
(kW)
---
0.2 (0.37) 0.4 (0.55) 0.75 (1.1) 1.5 (1.5)
Output
specifi-
Rated output capacity
(kVA)
---
0.9
1.4
2.6
3.7
cations
Rated output current (A)
---
1.2
1.8
3.4
4.8
Rated output voltage
Three-phase, 380 to 460 VAC
(Corresponds to the input voltage)
Maximum output
frequency
400 Hz (Parameter setting)
Cooling method
Self-cooling
H
General Specifications
Installation type
Panel mounting
Installation site
Indoor (free from corrosive gases and dust)
Ambient temperature for
operation
–10
°
to 50
°
C
Humidity
90% or less (no-condensing)
Ambient temperature for storage –20
°
to 60
°
C
Altitude
1,000 m max.
Vibration resistance
Less than 20 Hz: 1G {9.8 m/s
2
} or less
20 to 50 Hz:
0.2G {1.96 m/s
2
} or less
Cable length between Inverter
and motor
100 m max.
Specifications
Chapter 6
Содержание SYSDRIVE 3G3EV SERIES
Страница 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Страница 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Страница 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Страница 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Страница 32: ...Chapter 4 Preparing for Operation 4 1 Preparation Procedure 4 2 Using the Digital Operator 4 3 Test Run 4...